Horse Power - Ampre Table
| Approximate Horsepower |
120 Volts |
240 Volts |
| Full Load |
Locked Rotor |
Full Load |
Locked Rotor |
| 1/4 |
AC |
4.4 |
26.4 |
2.2 |
13.2 |
| |
DC |
— |
— |
— |
— |
| 1/4 |
AC |
5.8 |
34.8 |
2.9 |
17.4 |
| |
DC |
2.9 |
29.0 |
1.5 |
15.0 |
| 1/3 |
AC |
7.2 |
43.2 |
3.6 |
21.6 |
| |
DC |
3.6 |
36.0 |
1.8 |
18.0 |
| 1/2 |
AC |
9.8 |
58.8 |
4.9 |
29.4 |
| |
DC |
5.2 |
52.0 |
2.6 |
26.0 |
| 3/4 |
AC |
13.8 |
82.8 |
6.9 |
41.4 |
| |
DC |
7.4 |
74.0 |
3.7 |
37.0 |
| 1 |
AC |
16.0 |
96.0 |
8.0 |
48.0 |
| |
DC |
9.4 |
94.0 |
4.7 |
47.0 |
| 1 1/2 |
AC |
20.0 |
120.0 |
10.0 |
60.0 |
| |
DC |
13.2 |
132.0 |
6.6 |
66.0 |
| 2 |
AC |
24.0 |
144.0 |
12.0 |
72.0 |
| |
DC |
17.0 |
170.0 |
8.5 |
85.0 |
| 3 |
AC |
34.0 |
204.0 |
17.0 |
102.0 |
| |
DC |
25.0 |
250.0 |
12.2 |
122.0 |
| 5 |
AC |
56.0 |
366.0 |
28.0 |
168.0 |
| |
DC |
— |
— |
20.0 |
200.0 |
| 7 1/2 |
AC |
80.0 |
480.0 |
40.0 |
240.0 |
| |
DC |
— |
— |
29.0 |
290.0 |
* Locked rotor ratings shown are 6 times full load on AC and 10 time full load on DC. The
above chart is offered as a guide only, as all motors do not necessarily come within the
maximum ratings shown in the chart.
|
|